Simulation
The applet below can be run with the default parameters. To set any parameter,
click on the arrow pointing downwards beside the Peak Source Voltage,
a menu would appear. The default value of the parameter highlighted
appears in the textfield for Set Value. To change the parameter,
select the parameter and then click within the editable textfield for Set
Value. In order to change this parameter, you must click on Set
Value button. You can set the desired response to be one of three
responses.
An example is presented now to explain how the per unit values can be set.
Let a 3 phase, 415 V, 50 Hz source supply power to the converter. Then the
maximum average voltage that can be obtained is presented in equation (10).
Let the nominal rated dc link current be 100 A. Then the nominal load resistance
or the base impedance for the system is assigned as shown by equation (11).
Given that the current through the load is free of ripple, the rms line current
is obtained according to equation (12) and this value includes both the fundamental
component and the harmonic components. The fundamental rms component is obtained
as illustrated by equation (13). Given that the dc link inductance is 10 mH,
its p.u. value is obtained as shown by equation (14).
Given that the line inductance is 1 mH, its p.u. value is obtained as shown
by equation (16). Usually the line inductance is called as the 4% reactor,
implying that when the line current is at its rated value, the rms value of
the fundamental component of voltage across the line reactor is 4% of the
phase voltage. For example, if the rms phase voltage is 240 V, the drop across
4% reactor at rated current would be 9.6 V. When the line voltage is 415 V,
the phase voltage is obtained as shown by equation (16). The drop across the
line inductor can now be stated as a fraction of the phase voltage as given
by equation (17). This means that if the drop across the line inductor is
to be 4% of phase voltage, the inductance should be 0.4 mH and not 1 mH.
It is possible to set the load resistance to a value other than its nominal
value. The nominal value of load resistance is 5.6 W.
If the load resistance is to be 10 W, then set
Load Fraction as shown by equation (18).
click here to open the applet
TO THE TOP |