PCTR-10kW-48V |
|
48V / 200A |
|
|
480VAC, 3-Phase ±10% Delta Connection with Earth Ground |
|
47-63 Hz |
|
13.8 A rms / phase at 480VAC |
|
>0.95 |
|
<25Apk per phase |
|
25A input fuses |
|
|
48V Nominal, 40-62.5V Max. |
|
200A Max. |
|
10 kW Max. |
|
110% |
|
< 200 mVpp (100kHz Bandwidth)
< 2mV psophometric |
|
92% |
|
|
Voltage control with current limit |
| |
|
Output Voltage Regulation |
|
±0.5% |
|
±5% passive |
|
Soft start, no overshoot |
|
|
- Under voltage
- Over Voltage
|
|
- Over Current
- Over Voltage
- Over temperature
- Reverse polarity protection (250A output fuse)
|
|
|
0 - 50ºC |
|
Air Cooled |
|
|
Isolated RS-232, RS-485 |
|
Fully Programmable Voltage and Current Limits |
|
Forced air, fans |
|
- 4U high
- Size: 19" Rack mounted, 20" deep
- Wt.: ~ 65lb
|
|
DTM UL 1950 |
|
DTM EN55022 |